Oil & Gas fired Hot Water Generator

New ‘R series’ Hot Water Generators come with all latest controls, safety, Ecological and combustion Technique. The design of these Generators has been perfected, employing more than 15 years experience in manufacturing high quality Electric and Gas fired Hot Water Generators and Steam boilers.

To achieve following features :-

  • Smaller in dimensions for installation even in Basement /Terraces with weather proofing enclosure.
  • Horizontal unit with/without calorifiers, skid mounted (foundation not required).
  • 3 pass design gives high efficiency of 93% ± 2% on N.C.V.
  • Very durable double coil of large diameter pipe (50 mm OD) ensures lesser coil choking (machine wound coil to avoid hot spat), coil available in S.S. (304/316) Copper as well.
  • Monoblock Burner of international repute, highly efficient, economic, excellent design for low noise operation.
  • Water/Glycol circulating Pump with mechanical seal for desired quantity
  • Pre insulated (No. Insulation required at site).
  • Non IBR.
  • Control panel pre wired, easy to operate for precise control of temperature with low Water level, over heating (Water and Flue). Flame failure protections with Audio visual Alarm.
  • Provision of economiser available for instant sanitary Hot Water/pre-heating. Feed water by recovering heat from Flue gasses (optional).
  • Hour counter meter for monitoring Fuel consumption and record maintenance.

MODEL

Coil Type

RT-10

RT-20

RT-30

RT-40

RT-60

Output

KW

Kcal/Hr (in thousand)

116

100

232

200

348

300

465

400

697

600

Net Efficiency

%±2%

93.0

93.0

93.0

93.0

93.0

Flow rate

M³/hr

10

12.5

16

20

30

Max. Operating Pressure

Bar

10

10

10

10

10

Outlet temperature

C (Max)

90

90

90

90

90

Installed Electrical Load

KW

2.66

2.66

4.25

4.4

7.0

Power supply

415V ±6%, 50 Hz 3 phase, 4 wire

220V-50 Hz Single Phase 3 wire

🔘

🔘

🔘

🔘

🔘

🔘

Hour Meter

🔘

🔘

🔘

🔘

🔘

Fuel

HSD (10,500 KCAL/HR NCV)

🔘

🔘

🔘

🔘

🔘

Gas (LPG/Natural)

🔘

🔘

🔘

🔘

🔘

Burner Modulation

Hi – Lo – Off

On – Off

🔘

🔘

🔘

🔘

🔘

🔘

HSD consumption

Kg/Hr

10.5

20.5

31

41

62

LPG consumption

Kg/Hr

8.4

16.8

25.2

33.6

50.4